← DELTA-100 site · live plant simulator
Net export
BPDB dispatch
Binding limit
Alarms

Concept-stage simulation for discussion with BPDB. Equipment figures are engineering assumptions pending OEM data and a feasibility study, and the 100 MW net output is not verified. Edit the assumptions at the bottom of the page and the whole plant recalculates.

Plant floor

Bay of Bengal Site boundary · ~10 acres (concept allowance) Admin · Engine control room T-1T-2 Settling · Day Separators HFO storage & treatment Engine hall Heat recovery · ST EGB-1EGB-2 ST-G Condenser Aux B Seawater pumphouse Step-up · Switchyard GT-1GT-2 To national grid · 132 kV (assumed)
Fuel oil Exhaust gas Steam Seawater Electrical power Flow speed follows the live rate
Instructor station · inject a fault

Can DELTA-100 deliver 100 MW?

Each bar is the most net power the plant could export if only that system limited it, under current conditions. The yellow tick is the 100 MW target. Click a row to open that area.

Net export trend

ExportDispatch100 MW target

Alarms

Design assumptions (edit to test the design)

Model notes: engine fuel consumption follows a typical large two-stroke curve (about 170 g/kWh near full load); exhaust leaves the turbochargers at 215–260 °C and the exhaust gas boilers cool it no lower than the acid dew point setting; about 27% of engine fuel energy goes to the cooling water; HFO viscosity follows a 380 cSt grade. Benchmark from public records: Baraka Patenga, 50 MW, Tk 415 crore historical project cost, 3.2 MW waste-heat steam turbine.

DELTA-100 concept simulator. All imagery is a schematic visualization, not an engineering drawing.